SEARCH

Central heating with zone valves

A central heating system provides heat to a building from a centralised location, typically treating the entire building as a whole and relying on one temperature setting and reading to know when to turn the heat on or off. This can be very inefficient and only accurately controls the temperature in the room where the thermostat is placed. Creating zones within a building is a way to increase efficiency and temperature comfort level, as it gives better control on when and where the hot water is going through your radiators, as fluid control specialist Tameson explains.

Example home using two zones for its central heating system.

To better understand how these systems work, please look at the example pictured. It shows a two level house with Zone A and Zone B, each controlled by separate thermostats on their respective level and set, or put on a schedule, individually to the desired temperature for that floor. When the thermostat’s settings determine it is time to heat the room, it sends an electrical signal to a zone valve to open the flow of hot water to this zone.

Some zone valves include auxiliary limit switches to determine if the valve is completely open or closed. These systems use these signals to control a pump (circulator) and boiler to start pumping the hot water. The water then flows through the system, heating the zone, until the respective thermostat’s temperature setting is reached. Once reached, it will send a final electrical signal to close the valve, which releases the limit switch. The hot water then stops flowing through this zone.

Zone valve heating system design considerations

An existing central heating system can be modified to incorporate zones, or a new system can have them from the beginning. There are design considerations that should be taken into account to ensure the system works properly for the life-time of the system.

Zone valve type: An electrical ball valve is one of the preferred types of zone valves due to its durability, slow close to prevent a water hammer, low power consumption, and high reliability. An internal ball with a bore gets rotated a quarter turn by an electric motor when the appropriate signal is received to either open or close the valve. When it is in the open or closed state, it does not require additional electricity to remain in that state. Often times, the valve can also be manually operated by a lever in case of a power failure or for testing.

Valve material: Due to the high temperature of the water, certain materials need to be used for both the housing and the seal. It is recommended that the valve’s housing material be brass, the O-rings be EPDM (ethylene propylene diene monomer) and the seal material be PTFE (Teflon) to ensure proper functionality through the system’s life.

Location of zone valves: A zone valve can be located right after the boiler and circulator (hot side), or at the end of the zone circuit (cold side). If possible, it is recommended to locate the valve on the cold side as it will be less damaging to the valve and improve its life-time.

Location of thermostat: As previously discussed, each zone needs its own individual thermostat to control the temperature. It should be away from an immediate heat source within that zone.

Water pressure: A building’s size, length of heating pipes, pressure drop due to valve orifice, and amount of zones need to be taken into consideration to ensure that the circulation pump can create enough pressure to move the water through all of the zones.

Maintenance: Ensure the valves are easily accessible in case a failure does occur and maintenance is required. Common failure methods are:

  1. Over heating: This is typically due to a lack of proper ventilation for heat dissipation. Often, removing the cover is a quick solution, but should not be a long-term one as eventually the motor will fail.
  2. Burnt motor: Frequent over heating or the wrong voltage/current can destroy the electric motor. The power supply, wiring, and the cause of the burnt motor needs to be checked before replacing the motor.
  3. Leaking or unable to open: An internal component is failing and the valve needs to be replaced. You should perform monthly checks by actuating the valve to ensure it is still working properly, as opening torque can build up over time.

Find out more about Tameson at www.tameson.co.uk

23 August 2018

Comments

Already Registered?
Login
Not Yet Registered?
Register
ACR News

Airtech offers radon solutions for social housing

Ventilation specialist Airtech Environmental Systems recently supported UK Radon Awareness Week from 5-11 November 2018. Run by the UK Radon Association, the theme for the 2018 campaign was Healthy Living with a focus on raising awareness of how ...

  14-Nov-2018

Webinar: How to avoid the most common pitfalls when installing HVAC sensors

Choosing the right instrument for your HVAC application and needs is important, but it is just as vital to make sure that your HVAC device is installed correctly, says Vaisala....

  06-Nov-2018

Commercial Heating Solutions

Vokèra by Riello releases new Commercial Heating Solutions catalogue.
  09-Nov-2018
Heating & Ventilating Review is the number one magazine in the HVAR industry. Don’t miss out, subscribe today!
Subcribe to HVR

Diary