Heating and Ventilating

 

NHS Surrey cuts carbon emissions with heating and HW upgrade

With the aim of reducing carbon emissions and improving efficiencies, NHS Surrey embarked on a programme of upgrade to their heating and hot water systems across more than twenty sites. Many of the boilers and water heaters were coming to the end of their economical lifespan so it was an ideal time to review their heating and hot water plant.
Gary White, programme manager at Surrey Primary Care Trust (PCT), said: 'As well as needing to replace plant that was coming to the end of its life we were looking to lower energy bills and reduce carbon emissions across all sites in line with the NHS Carbon Reduction Strategy for England. The Trust Estates Department wanted to standardise boilers and equipment across the different sites and due to the diverse range of products that Hamworthy Heating offer we were able to choose the most suited boiler and water heater for each application.'

One of the sites, Molesey Hospital, a 20-bed hospital part of the Surrey NHS PCT required a full plant room refurbishment. Southampton based ARB Mechanical Engineering, the contractor for the project, replaced three gas fired atmospheric boilers with two Purewell VariHeat 70kW gas fired condensing boilers. Two Dorchester DR-FC Evo 30 direct fired condensing water heaters were also installed to provide highly efficient hot water generation.

Hugo Jimenez, senior mechanical designer at MCA Consulting, specified the equipment and commented: 'We chose to separate the heating and hot water for this application due to the 24/7 demands placed on the system and the requirement for critical hot water to get to temperature very quickly. The condensing water heaters provide exactly what we needed for this project and the robustness of the Purewell VariHeat boilers means they are more than capable of dealing with the demands faced by the system over a long period of time.'

The three atmospheric on/off boilers that were removed gave a total output of 123kW, with a 3:1 turndown ratio and seasonal efficiencies of 78 per cent.

Hamworthy said: 'Compare this with the two new fully modulating condensing boilers that provide a total output of 140kW, 7:1 turndown ratio and seasonal efficiencies of 95 per cent and you can clearly see the efficiency improvements and consequential carbon reduction.

'Take into account the corresponding reduction in service and maintenance costs from lowering the number of boilers plus the fully modulating operation that allows accurate load matching and you have a very attractive proposition for the life of the boiler.'

The hot water for the hospital is now provided by two condensing water heaters with a total continuous output of 1,260l/h, thermal efficiencies of 98 per cent. Each water heater is fitted with a top-to-bottom recirculation kit for operating during the legionella protection cycle to reduce the likelihood of legionella bacteria forming particularly in this application where occupants are more susceptible to the harmful effects of legionella.

www.hamworthy-heating.com
14 May 2013

Comments

Already Registered?
Login
Not Yet Registered?
Register

FETA welcomes guests to Annual Luncheon

The 2024 FETA Annual Luncheon took place on Thursday 11th April and attracted guests from across the heating, ventilation, building controls, refrigeration and air conditioning industries as well as individuals from related institutions, ...

  25-Apr-2024

Prizes galore to be won on Conex Bänninger’s interactive stand

Conex Bänninger, a global leader in the manufacture of high-quality fittings, valves and accessories, will have an enhanced interactive stand (5D19) at InstallerShow 2024....

  25-Apr-2024

STOKVIS R600

CONDENSING ULTRA LOW NOx PREMIX COMMERCIAL BOILER
  10-Jan-2019
Heating & Ventilating Review is the number one magazine in the HVAR industry. Don’t miss out, subscribe today!
Subcribe to HVR

Diary

HVR Awards 2024
https://www.heatingandventilating.net/nhs-surrey-cuts-carbon-emissions-with-heating-and-hw-upgrade