The Albion ART 25 is a fixed orifice double regulating valve used to regulate and measure the flow passing through it.
Installation:Fixed orifice double regulating valves must always be installed with a minimum of 5 pipe diameters of straight pipe, without intrusion, upstream of the orifice plate. Downstream of the valve a minimum of 2 pipe diameters of straight pipe are required.
SizingOnce the required flow rate has been calculated, the size of the fixed orifice double regulating valve can be determined based on the following: The minimum signal at the design flow rate of 1 kPa.
For minimum pressure loss, a maximum signal of 4.7 kPa, which corresponds to the maximum differential pressure range of a fluorocarbon manometer.
Pressure
Equipment
DirectiveUnder the Pressure Equipment Directive (PED) these fixed orifice double
regulating valves have been specified for Group 2 Liquids i.e. non-hazardous. Sizes 1/2" to 2" are classified as SEP (Sound Engineering Practice)
ConnectionBSP Parallel F/F Ends
Pressure16 Bar Rated
Temperature-10°C to +120°C
Approvals/otherEPDM Seat
Gate Valve
Part No.ART 175
DescriptionBrass Gate Valve 25 Bar Rated
ConnectionBSP Taper F/F Ends
Pressure25 Bar Rated
Temperature-20°C to +180°C
Approvals/otherFull Bore BS 5154 Approved Kite Marked KM 553179
Globe Valve
Part No.ART 350
DescriptionBronze Globe Valve
ConnectionBSP Taper F/F Ends
Pressure32 Bar Rated
Temperature-10°C to +200°C
Approvals/otherBS 5154 Approved. Renewable PTFE Seat
Flexible Connectors
Part No.ART 430/440
DescriptionFlanged Flexible Connector
ConnectionFlanged PN16
Pressure16 Bar Rated
Temperature-20°C to +100°C EPDM
-20°C to +80°C NBR